All products presented on this website are subjected to extensive checks from our team of engineers and mechanics. Althought,we can not offer a full guarantee for any of our products, as they are used parts from third parties. The limited liability guarantee that comes with these products is extensively analysed here. Please contact our Support Lineif you have any questions about our products guarantee.
ℹ️ Additional Information
Condition |
USED/EXCELLENT CONDITION |
---|---|
Manufacturer |
EMERSON |
Product Code |
100.199.00251 |
📦 Guarantee Terms
🗂️ Product Files
🖹 Description
The Fisher 646 electro-pneumatic transducer uses a converter module that converts a 4 to 20 milliampere
input signal to a proportional 0.2 to 1.0 bar (3 to 15 psig) pneumatic output signal. The converter module uses small parts of minimum mass, which are balanced symmetrically around a pivot point at the center of the mass. This balanced arrangement results in a high performance instrument that reduces sensitivity to vibration.
Input Signal:4 to 20 mA DC, constant current with 30 VDC maximum compliance voltage
Output Signal:0.2 to 1.0 bar (3 to 15 psig) direct acting only
Supply Pressure
Recommended: 1.4 bar (20 psig)
Minimum: 1.4 bar (20 psig)
Maximum: 3.4 bar (50 psig)